INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on theTechnologic 5
10BINARY INPUTTechnologic 5500BACnet Property Return Data Type Range Required WritableObject_IdentifierOctet String Octet(4) Yes NoObject_Name Charact
11BACnet Communication Objects ListObject Identifier Object Name Object Type Present Value/Range UNITS UsedBinary Input, 1 P1 Overload Failure BINARY_
12BACnet Communication Objects List (continued)Object Identifier Object Name Object Type Present Value/Range UNITS UsedBinary Input, 54 AI #4 Failure
13BACnet Communication Objects List (continued)Object Identifier Object Name Object Type Present Value/Range UNITS UsedAnalog Value, 34 Setpoint #6 AN
14NoNoNoCorrect the WireConnections.Correct the MAC address.The polling device must set thedevice instance number = 100 onthe slave unit.Check MAC add
15Section 3JOHNSON CONTROLS N2 COMMUNICATION POINTS LISTNPT NPA Point Description Range/Value UnitsBI 1 Pump #1 Overload Failure 1 = Failure
16JOHNSON CONTROLS N2 COMMUNICATION POINTS LISTNPT NPA Point Description Range/Value UnitsBI 60 Analog Input #10 Failure 1 = Failure 0 = O.K.
17NoNoNoCorrect the wireconnectionsChange the node numberas defined by the JCtechnicianThe JC device requires the JC DLL file for the Technologic cont
18Section 4MODBUS Communication Points ListFunction ModbusCode Points # Point Description Range/Value Address Units02 1 Pump #1 Overload Failure 1 = F
19MODBUS Communication Points List (continued)Function ModbusCode Points # Point Description Range/Value Address Units02 60 Analog Input #10 Failure 1
2SECTION 1 - GENERAL Page Purpose of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20NoNoCorrect the wireconnectionsChange to correct nodenumberYesYesView “COMMUNICATION” test screenIs Node number settingcorrect?Range 1 -253Is RS485
21Section 5BACnet IP Protocol Implementation Conformance StatementVendor Name: Bell & GossettVendor ID: 84Product Name: Technologic 5500 Pump Cont
22BACnet Standard Application Services Supported - cont.Application Initiate ExecutesService Requests RequestsAtomicReadFile □ □AtomicWriteFile □ □Add
Standard Object Types Supported Object Type SupportedDynamically DynamicallyOptionalWritableCreatable DeleteablePropertiesPropertiesSupportedAnalog In
24ANALOG INPUTTechnologic 5500BACnet Property Return Data Type Range Required WritableObject_IdentifierOctet String Octet(4) Yes NoObject_Name Charact
25BINARY INPUTTechnologic 5500BACnet Property Return Data Type Range Required WritableObject_IdentifierOctet String Octet(4) Yes NoObject_Name Charact
26Technologic 5500BACnet Communication Objects ListObject Identifier Object Name Object Type Present Value/Range UNITS UsedBinary Input, 1 P1 Overload
27Technologic 5500BACnet Communication Objects List (continued)Object Identifier Object Name Object Type Present Value/Range UNITS UsedBinary Input, 5
28Analog Value, 38 Setpoint #10 ANALOG_VALUE 0 to Span (in Technologic User Setup Menu)Analog Value, 39 Setpoint #11 ANALOG_VALUE 0 to Span (in Techno
29NoNoNoConnect Ethernet cable.Correct IP address in TechController.Correct subnet address inTech Controller.Call Factory for help.YesYesYesYesYesBACn
3PURPOSE OF MANUALThis manual is furnished to acquaint you with some of thepractical ways to install, operate, and maintain this unit. Readit carefull
RACK OSERIAL COMMUNICATIONOPTIONAL I/OOPTIONAL I/ODIGITAL INPUTANALOG INPUTANALOG OUTPUTRACK 1RS COMMUNICATION DETAILDATAn_DATAIF321 SERIAL COM1
Xylem Inc. 10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861www.xyleminc.com/brands/bellgossettBell & Gossett is a t
4COMMUNICATION SETUP TABLE & TESTINGSee the following table for all communication menu items.COMMUNICATION MENU ITEMSFieldMenu Item Variable Defau
5There may have been additional protocols added to the communication setup menu, contact your Bell & Gossett representative concerning additional
6BACNET MSTP PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENTVendor Name: Bell & GossettVendor ID: 84Product Name: Technologic 5500 Pump ControllerPr
7BACnet Standard Application Services SupportedApplication Initiate ExecutesService Requests RequestsAcknowledgeAlaramConfirmedCOVNotificationConfirme
8Standard Object Types Supported OptionalDynamically Dynamically Properties WritableObject Type Supported Creatable Deletable Supported PropertiesAnal
9ANALOG INPUTTechnologic 5500BACnet Property Return Data Type Range Required WritableObject_IdentifierOctet String Octet(4) Yes NoObject_Name Characte