Bell-gossett V01348H Comfort Trol Zone Control Valve User Manual

Browse online or download User Manual for Accessories for water Bell-gossett V01348H Comfort Trol Zone Control Valve. Bell & Gossett V01348H Comfort Trol Zone Control Valve User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
PERFORMANCE CHARACTERISTICS:
Maximum differential shut off pressure: 35 PSIG
WORKING PRESSURE & TEMPERATURE LIMITS
(SOLDER TYPE LIMITS FOR ASTM STD. B16.18)
Maximum ambient temperature: 125°F.
Electrical rating: 24 Volt 50/60 Cycle, 1Ø, 15VA AC
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
Comfort-Trol
®
Zone Control Valve
SAFETY
INSTRUCTION
This safety alert symbol will be used in this manual to draw attention
to safety related instructions. When used, the safety alert symbol
means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!
FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A
SAFETY HAZARD.
DESCRIPTION
A two wire heat motor operated valve designed for Hydronic Heating/
Cooling Systems.
THERMOSTAT
24 Volt two wire with 0.6 ampere heat anticipator setting.
TRANSFORMER
115/24 volt rated at 40 VA for a maximum of three Comfort-Trol Zone
Valves. Note: This transformer must be dedicated to the Comfort-Trol
Zone Valves and not be used to power any other device.
CAUTION: Heat associated with the use of silver solder will
damage the Comfort-Trol and void the product warranty.
Use only the low temperature solder specified. Failure to follow
these instructions could result in property damage and/or moder-
ate personal injury.
WARNING: Solder joints will fail if used at pressures or tem-
peratures above those listed in the above table. Do not
exceed the temperature and pressure limitations. Failure to follow
the above instruction can cause the joint to fail resulting in serious
personal injury and/or property damage.
WARNING: Hazardous conditions could occur if the follow-
ing notes are not adhered to:
WARNING NOTES:
READ PRIOR TO INSTALLING COMFORT-TROL
1. Do not install Comfort-Trol in a dusty area or in an area where
the flow of air to the operator is restricted because erratic
operation or premature failure may occur.
2. Use 95-5 (Tin-Antimony) solder and a good grad of flux to
solder the Comfort-Trol valve body into the system.
NOTE: a. Remove the brass bonnet and retainer assembly
from the valve body before applying heat to the
body. Failure to do so will damage the valve seals
and discs.
b. Excessive use of solder in a vertical installation may
result in damage to the valve seat.
c. Avoid excessive use of flux.
d. Heat associated with the use of silver solder may
damage the Comfort-Trol.
3. Do not install a jumper wire between terminals #1 and #2
because the thermostat heat anticipator may burn out when
the Comfort-Trol operator is energized.
4. Keep external wiring from contacting the Comfort-Trol operator
cover by securing the wiring to a nearby support.
5. Use only silicone grease to lubricate the valve gland pin and
O-ring seals. Do not use lubricants with a petroleum base. The
use of a petroleum base lubricant will cause swelling and fail-
ure of U-rings.
6. Do not insulate the Comfort-Trol Zone Valve Operator.
7. Use of additives to the system may be harmful to the Comfort-Trol.
Failure to follow these instructions could result in serious personal
injury or death and property damage.
PATENT NO’S. 4,553,733 AND 4,560,140
TYPE OF
MAXIMUM LIMITATIONS
SOLDER PRESSURE PSI TEMPERATURE °F
95-5
TIN- 125 240
ANTIMONY
WARNING LABEL PART NO. V56871
INSTALLED IN THIS LOCATION.
IF MISSING IT MUST BE REPLACED.
05263:V01348 11/11/02 6/17/09 1:33 PM Page 1
INSTRUCTION MANUAL
V01348H
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Zone Control Valve

PERFORMANCE CHARACTERISTICS:Maximum differential shut off pressure: 35 PSIGWORKING PRESSURE & TEMPERATURE LIMITS(SOLDER TYPE LIMITS FOR ASTM STD.

Page 2 - MANUAL OPERATION

NOTE: After power is restored, return the Comfort-Trol to normaloperation by:1. Assembling the operator to the valve by installing the operato

Page 3 - SERVICE INSTRUCTIONS

3SERVICE INSTRUCTIONSComfort-Trol Zone Control Valves are designed for fast and easy main-tenance with a standard screwdriver and pliers. It i

Page 4 - Xylem Inc

COMFORT-TROLVALVE BODYFIG. 3V01372BONNET &RETAINERASSEMBLYBONNET &RETAINERASSEMBLYLESS SEALGLANDSEAL GLANDABCD189139 (CARTON OF6 V01372)SPREAD